Shopping security
The Allen-Bradley 1747-SN/B, also cataloged as the 1747-SN Remote I/O Scanner Module, operates as a dedicated hardware component for distributed network communication management within SLC 500 Modular Controllers platforms.
| Parameter | Specification |
|---|---|
| Model | 1747-SN |
| Brand | Allen-Bradley |
| Origin | USA |
| Weight | 0.25 kg (Shipping Weight 2 kg) |
| Dimensions | Standard SLC 500 single-slot module footprint |
| Operating Temp | 0 to +60 deg C (+32 to +140 deg F) |
| Power Consumption | Backplane load: 600 mA @ 5 VDC, 0 mA @ 24 VDC |
| Communication Protocol | Universal Remote I/O (RIO) |
| Baud Rate Range | 57.6 kbaud, 115.2 kbaud, 230.4 kbaud |
| Humidity | 5 to 95% non-condensing |
| Noise Immunity | NEMA Standard ICS 2-230 |
| Hazardous Location Rating | Class I, Division 2, Groups A, B, C, D |
| Certifications | UL, C-UL, CE, C-Tick, IECEx |
The 1747-SN governs cyclic network data exchange synchronized with the backplane bus communication velocity properties of the local SLC chassis. By serving as an interface controller, the hardware facilitates wide-area I/O density scaling routines, bridging remote adapters and rack assemblies over deterministic physical pathways. Integrating this scanner within hybrid architectures alongside newer Profinet / EtherNet/IP deterministic networks requires strict verification of firmware flash compatibility across the host SLC processor and communication bridges to prevent token-rotation latencies, transmission drops, or remote block mapping faults.
Q: Does the 1747-SN support online extraction or Insertion Under Power (RIUP)?
A: No. The SLC 500 backplane infrastructure does not support hot-swapping. The rack power supply must be entirely isolated before inserting or removing the module. Attempting installation while the backplane is energized can cause physical degradation of internal logic components or network port transceivers.
Q: What are the layout constraints regarding network line termination for this module?
A: The RIO link requires appropriate resistor termination at both physical ends of the trunk line to eliminate signal reflections. The specific resistance value (82 Ohm or 150 Ohm) must be selected according to the baud rate configuration (57.6, 115.2, or 230.4 kbaud) and cable type utilized.